Fire Alarm Battery Calculation: Worked Example
How to size fire alarm standby batteries under NFPA 72: 24 hour standby, 5 minute alarm, the 1.25 aging factor that replaced the old 20 percent margin, and a full worked example.
Battery calculations show up on the NICET exams and in every shop drawing review. They are simple arithmetic, but one detail trips people up: is the safety margin 20 percent or 25 percent?
The short answer is that current editions of NFPA 72 use a 1.25 correction factor for battery aging, which is a 25 percent increase. Older editions used 20 percent.
Below is the method, one worked example and the edition history. This site is an independent practice trainer, not affiliated with NFPA or NICET, and the example is for study, not for a real design.
In short
- Size the battery for 24 hours of standby plus 5 minutes of alarm, or 15 minutes for in-building emergency voice systems.1
- 2022 edition: multiply the total by 1.25 for aging. That equals dividing by 0.80.23
- 2019 and earlier: add a 20 percent margin (multiply by 1.2).2
- Round up to the next standard battery size.
The method
- Add up the standby current of every device on the circuit, in amps.
- Add up the alarm current with all required notification appliances on.
- Multiply standby amps by 24 hours to get standby amp-hours.
- Multiply alarm amps by the alarm time in hours (5 minutes is 5/60 of an hour).
- Add the two results.
- Multiply by the aging correction factor.
- Choose the next standard battery size above the result.
The 24 hour capacity requirement sits in NFPA 72 section 10.6.7.2.1, and the alarm period in 10.6.7.2.2.3 Always check the edition your authority adopted.
Worked example
A panel with its devices draws 0.320 A in standby and 1.450 A in alarm.
| Step | Calculation | Result |
|---|---|---|
| Standby | 0.320 A x 24 h | 7.68 Ah |
| Alarm (5 min) | 1.450 A x 5/60 h | 0.121 Ah |
| Total | 7.68 + 0.121 | 7.80 Ah |
| With 1.25 aging factor | 7.80 x 1.25 | 9.75 Ah |
| Standard size | next size up | 12 Ah |
With the old 20 percent margin, the same system needs 7.80 x 1.2 = 9.36 Ah. It still lands on a 12 Ah battery here, but with a different load the two methods can pick different sizes.
If the system is an in-building emergency voice alarm, the alarm period is 15 minutes. Then 1.450 A x 0.25 h = 0.363 Ah, the total is 8.04 Ah, and 8.04 x 1.25 = 10.05 Ah. That is still a 12 Ah battery, but the margin to the battery rating is smaller.1
20 or 25 percent?
Through the 2019 edition, NFPA 72 told designers to add a 20 percent safety margin. For the 2022 edition, the technical committee replaced it with a correction factor of 1.25 for aging, so the battery still meets the load at the end of its service life.2
The reasoning is straightforward. A lead-acid battery is considered at end of life when it has about 80 percent of its rated capacity, and 1 divided by 0.8 is 1.25. The committee also noted that new batteries may start below full capacity and that other battery types need their own factors.2
Secondary sources cite the 2022 rule as section 10.6.7.2.14.34 The 2025 edition appears to keep the 1.25 factor, as its revision reports show no change to it, but we have not checked the final 2025 text. Verify in the edition you use. NICET exams currently use the 2022 edition.5
Common mistakes
- Using 5 minutes where the system needs 15.
- Applying the margin to standby only.
- Forgetting the load of remote power supplies and relays.
- Rounding down instead of up.
- Using the old 20 percent figure on a 2022 exam question.
Practice with a free practice test, or see the Level II trainer, where power calculations are part of the layout domain.
Common questions
Is it 20 percent or 25 percent?
25 percent (a 1.25 factor) under the 2022 edition. The 20 percent margin belongs to 2019 and earlier editions.
Is 1.25 the same as dividing by 0.8?
Yes. Multiplying by 1.25 and dividing by 0.80 give the same answer.
Do I use 5 or 15 minutes of alarm?
5 minutes for most systems, 15 minutes for in-building emergency voice/alarm communications.
Which edition does NICET use?
The current NICET FAS exams are based on NFPA 72 (2022). Check the Level II guide for the planned update.
Sources
Always confirm section numbers in the edition adopted by your jurisdiction.
- Battery calculations for fire alarm systems, Fire Tech Productions (blog.firetech.com)
- NFPA 72 A2021 first draft report, SIG-FUN (nfpa.org)
- Fire Tech Productions, May 2026 (blog.firetech.com)
- Key changes to NFPA 72 in 2022 and 2025, InspectPoint (inspectpoint.com)
- NICET FAS program page and reference lists (nicet.org)